7 Start-Up
System Manual Modular Systems
Page 84 of 114
HI 800 191 E Rev. 2.02
To connect signals to inputs and outputs
1. Select the Signals menu option to open Signal Editor of the ELOP II Factory's Hardware
Management.
2. Right-click the HIMatrix I/O module and select
Connect Signals
from the context menu.
A dialog box for connecting the signals in the Signal Editor to the available hardware
channels appears and contains the tabs
Inputs
and
Outputs.
3. If required, select the
Inputs
tab.
4. Position the two dialog boxes adjacently to get a better overview.
5. Drag the signals onto the inputs located in the
Signal Connections
pane.
6. To connect the signals to the outputs, select the
Outputs
tab and proceed as described for
the inputs.
The signals are connected to the inputs and outputs.
The following example is based on the list provided in Table 33 and the procedure described
above.
Configuring Pulsed Outputs and Connecting them to the Inputs
The following table shows the connection of the input module's output signals to signals:
System signal (output signal)
Signal
DI Number of Pulsed Outputs
Sum_Pulse
DI Slot Pulsed Outputs
Board_POS_Pulse
DI Pulse Delay [µs]
Pulse_delay
DI[xx].Pulse Output of 4 (=
Sum_Pulse)
consecutive output signals
T1…T4
Table 51: Connecting Signals to the Input Module's Output Signals
Digital inputs (pulsed channels) may be arbitrarily connected to the pulsed outputs depending
on the hardware configuration.
Connecting the Signals to the Inputs and Corresponding Error Codes
For each useful signal
DI[xx].Value,
the relevant error code
must also be evaluated
The following table shows the signals to be connected for each of the input channels to be
monitored:
System signals
Signals
DI[xx].Value
of the corresponding channel
xx
S1_1_pulsed…S2_2_pulsed
(one of the signals
per channel)
DI[xx].Error Code
of the corresponding
channel xx
FC_S1_1_pulsed…FC_S2_2_pulsed
(one of the
signals per channel)
Table 52: Connecting Signals to the Input Module's Input Signals
Activation of Pulsed Outputs
For pulsed outputs of the output module, connect the
DO[xx].Value
output signals of the
corresponding consecutive channels to the
Pulse_ON
signal.
The logical value of the signal
Pulse_ON
is TRUE. This results in pulsed outputs that are
permanently activated and only set to FALSE for the duration of the pulse actuation.
7.7.5
Generating the Code for the Resource Configuration
To generate the code for the resource configuration
1. Move to the ELOP II Factory Project Management and select the HIMatrix resource in the
project window.
2. Right-click the HIMatrix resource and select
Code Generation
on the context menu.