System Manual Modular Systems
7 Start-Up
HI 800 191 E Rev. 2.02
Page 73 of 114
Parameters for User Accounts
To set up new user accounts, the following parameters must be set:
Parameter
Description
User Name
User name or ID to log in to a controller.
The user name must not contain more than 32 characters (recommended: a
maximum of 16 characters) and may only be composed of letters (A ... Z, a ...
z), numbers (0 ... 9) and the special characters underscore «_» and hyphen «-
».
The password is case sensitive.
Password
Password assigned to a user name required for the log-in.
The password must not contain more than 32 characters and may only be
composed of letters (A...Z, a...z), numbers (0...9) and the special characters
underscore «_» and hyphen «-»
The password is case sensitive.
Confirm
Password
Repeat the password to confirm the entry.
Access Mode
The access modes define the privileges that a user may have.
The following access types are available:
Read: Users may only read information but they cannot modify the
controller.
Read + Operator: Similar to
Read
, but users may also:
Perform a download to load and start user programs
Configure the processor modules as redundant
Reset cycle time and fault or error statistics
Set the system time, force, restart and reset modules
Start system operation for processor modules.
Read + Write: Similar to Read + Operator, but users may also:
Create programs
Translate programs
Load programs into the controller
Test programs
Administrator: Similar to Read + Write, but users may also:
Load operating systems.
Modify the main enable switch setting
Change the SRS
Change the IP settings
At least one user must have administrator rights, otherwise the controller
settings are not accepted.
The administrator can revoke the user's permission to access a controller by
deleting the user name from the list.
Table 40: Parameters for User Accounts in the PES User Management Scheme
7.4.3
Setting up User Accounts
A user with administrator rights can access to all user accounts.
Observe the following points when setting up user accounts:
Make sure that at least one user account is assigned with administrator rights. Define a
password for the user account with administrator rights.
After a user account was created in the user management, its password must be used to
access and edit it.
In SILworX, use the
Verification
function to check the created user account.
The new user accounts are valid once the code has been generated and a download has
been performed to load the project into the controller. All the user accounts previously saved,
e.g., the default settings, are no longer valid.