7 Start-Up
System Manual Modular Systems
Page 92 of 114
HI 800 191 E Rev. 2.02
Figure 14: Peer-to-Peer Parameters in the
Inputs
Tab - CPU OS up to V7
4. The system parameters
Receive Timeout
,
Response Time
,
Connection State
and
Version
can be evaluated in the user program based on the signal assignment performed in the
Signal Editor.
The status signals can be evaluated in the user program.
To set a system signal from the user program
1. Right-click the resource in the ELOP II Factory Hardware Management and select
P2P
Editor
on the context menu to open it.
2. Select the row for the required resource.
3. Click the
Connect System Signals
button. The
P2P System Signals
window opens. Select
the
Outputs
tab
Figure 15:
Connection Control
System Signal in the
Outputs
Tab - CPU OS up to V7
The user program can set the
Connection Control
system signal.
7.8.3
Configuring the safe
ethernet
Connection
The following parameters can be set for a resource in the
P2P Editor
:
1. Profile - see below
2. Response Time
The response time is the time period that elapses until the sender of the message receives
acknowledgement from the recipient.