
System Manual Modular Systems
7 Start-Up
HI 800 191 E Rev. 2.02
Page 69 of 114
The
Write via MAC
dialog box appears.
6. Type correct values for the connection parameters and the SRS, and enter the access data
for a user account with administrator rights valid on the controller. Click
Write
.
Connection data and S.R.S are configured and it is now possible to log in.
For further details, refer to the SILworX manual First Steps (HI 801 103 E).
7.3.8
Loading a Resource Configuration after a Reset
If the compact system is switched on with engaged reset key, it restarts and resets the
connections parameters and user account to the default values (only in case of a controller).
After a new restart with disengaged reset key, the original values are used.
If the connection parameters were modified in the user program, they can be configured in the
compact systems such as described in Chapter 7.3.7.
Logging in as Default User
After configuring the connection parameters and prior to loading the user program, the default
user (administrator with empty password) must be used in the following cases:
The password for the user account is no longer known.
A new user account should be used in the project.
To log in as default user
1. Select the resource in the structure tree.
2. Click the
Online
button located on the Action Bar or select
Online
on the context menu.
The
System Login
dialog box appears.
3. In the
IP Address
field, select the correct address or use the MAC address.
4. Enter
Administrator
in the
User Group
field.
5. Let the
Password
field empty or cancel the password.
6. Select
Administrator
in the
Access Mode
field.
7. Click
Log-in.
SILworX is connected to the HIMatrix controller with default user rights.
Use
<Ctrl>+A
in the
System Login
dialog box to skip steps 4-6!
7.3.9
Loading a Resource Configuration from the PADT
Before a user program can be loaded with the connection parameters (IP address, subnet mask
and system ID) into the controller, the code must have been generated for the resource, and the
connection parameters for PADT and resource must be valid, see Chapter 7.3.7.
To load a resource configuration from the PADT
1. Select a resource in the structure tree.
2. Click the
Online
button located on the Action Bar or select
Online
on the context menu.
3. In the
System Login
dialog box, enter a user group with administrator rights or write access.
The Control Panel appears in the workspace and displays the controller state.
4. In the
Online
menu, select
Resource Download
.
The
Resource Download
dialog box appears.
5. Click
OK
to confirm the download.
SILworX loads the configuration into the controller.
6. Upon completion of the loading procedure, click the
Resource Cold Start
function on the
Online
menu to start the user program.
After the cold start,
System State
and
Program Status
enter the RUN state.
The resource configuration is loaded from the PADT.
The Start, Stop and Load functions are also available as symbols on the Symbol Bar.