7 Start-Up
System Manual Modular Systems
Page 66 of 114
HI 800 191 E Rev. 2.02
Name
Type
Description
Initial
Value
Remark
Sum_Pulse
USINT
Number of pulsed
outputs
4
1...8, as required
Board_POS_P
ulse
UDINT
Module slot with pulsed
outputs
2
With compact devices, the
DOs are used in slot 1, 2 or
3, see Table 35.
With the F60, the slot (3...8)
is given.
Pulse_delay
UINT
Pulse delay
400
Value in µs
Maximum value: 2000 µs
F20: Pulse delay must be ≥
500 µs.
Refer to the F20 manual.
T1
T2
...
T8
USINT
USINT
...
USINT
Pulse 1
Pulse 2
...
Pulse 8
1
2
...
8
Pulse 1...8, as required, must
match the number of pulsed
outputs.
Pulse_ON
BOOL
Initialization value for
pulsed outputs
TRUE
Activation of pulsed outputs
Table 33: Parameters for Line Control
The signal can be named freely; the names used in this manual are examples. All parameters
have the
Const
attribute.
The following table specifies the switch variables used in the example:
Name
Type
Description
Remark
S1_1_pulsed
S1_2_pulsed
BOOL
BOOL
Value
Value
First and second contact of
switch 1
S2_1_pulsed
S2_2_pulsed
BOOL
BOOL
Value
Value
First and second contact of
switch 2
FC_S1_1_pulsed
FC_S1_2_pulsed
BYTE
BYTE
Error code
Error code
Error codes for first and second
contact of switch 1
FC_S2_1_pulsed
FC_S2_2_pulsed
BYTE
BYTE
Error code
Error code
Error codes for first and second
contact of switch 2
Table 34: Switch Variables for Line Control
The following table specifies the slot numbers of modules with pulsed outputs when compact
devices are used.
Device
DI Pulse Slot
system parameter
F1 DI 16 01
1
F3 DIO 8/8 01
3
F3 DIO 16/8 01
3
F3 DIO 20/8 02
2
F20
3
F30
3
F31
3
Table 35: Module Slot with Pulsed Outputs
If the modular F60 system is used, the number of the slot in which the module with pulsed
outputs is inserted, must be used (3…8).
7.3.5.2
Configuring Pulsed Outputs
The pulsed outputs must begin in SILworX with channel 1 and reside in direct sequence, one
after the other.