Prerequisites
See the
Locations of drive blanks and thermal bezel blanks for components with thermal
on page 25 to:
1.
Identify the chassis model and system fan mode of the system you plan to install the component in.
2.
Determine if the accelerator is subject to thermal limitations in the identified system setup.
3.
Note the required drive bay action for the component installation.
Procedure
1.
Perform a backup of all critical server data and programs.
2.
If installed, remove the front bezel.
3.
Remove the drives and/or drives blanks from the bays noted in step 3 of the Prerequisites.
4.
Do one of the following:
• Install the LFF thermal bezel blanks.
• Install the LFF drive blank
• Install the SFF thermal bezel blanks.
24
Operations