Description
Chassis
Fan configuration Number of drives
supported by the server
Maximum inlet
ambient
temperature
Apollo r2800 Gen10
Chassis
(16 NVMe
backplane)
Redundant and
nonredundant
0 to 8 drives
35°C (95°F)
NVIDIA Tesla
P4 GPU
Apollo r2200 Gen10
Chassis
(12 LFF backplane)
Redundant and
nonredundant
5 to 6 drives
22°C (71.6°F)
5 to 6 drives
Not supported
0 to 4 drives
30°C (86°F)
Apollo r2600 Gen10
Chassis
(24 SFF or 16 SFF
+ 8 NVMe
backplane)
Redundant and
nonredundant
0 to 10 drives
28°C (82.4°F)
Apollo r2800 Gen10
Chassis
(24 SFF backplane
with SAS expander)
Redundant and
nonredundant
0 to 24 drives
28°C (82.4°F)
Apollo r2800 Gen10
Chassis
(16 NVMe
backplane)
Redundant and
nonredundant
0 to 8 drives
25°C (77°F)
NVIDIA Tesla
P40 GPU
Apollo r2200 Gen10
Chassis
(12 LFF backplane)
Redundant and
nonredundant
5 to 6 drives
Not supported
5 to 6 drives
Not supported
0 to 4 drives
25°C (77°F)
Apollo r2600 Gen10
Chassis
(24 SFF or 16 SFF
+ 8 NVMe
backplane)
Redundant and
nonredundant
0 to 10 drives
25°C (77°F)
Apollo r2800 Gen10
Chassis
(24 SFF backplane
with SAS expander)
Redundant and
nonredundant
0 to 24 drives
22°C (71.6°F)
Apollo r2800 Gen10
Chassis
Nonredundant
0 to 8 drives
25°C (77°F)
Table Continued
Specifications
173