7 Block OUTPUTS
Device Functions Proline Promag 55
98
Hauser
7.3.2
Function group OPERATION
OUTPUTS
E
⇒
CURRENT OUTPUT 1
EAA
⇓
CURRENT OUTPUT 2
EAB
⇓
PULSE/FREQ. OUTP. 1
ECA
⇓
PULSE/FREQ. OUTP. 2
ECB
⇓
RELAY OUTPUT 1
EGA
⇒
CONFIGURATION
470
⇓
⇓
OPERATION
474
RELAY OUTPUT 2
EGB
⇒
CONFIGURATION
470
⇓
OPERATION
474
Function description
OUTPUTS
➞
RELAY OUTPUT (1 to 2)
➞
OPERATION
ACTUAL STATUS RELAY
(4740)
Use this function to check the actual status of the relay output.
A jumper on the contact side defines the relay output as a normally open (NO or make) or
normally closed (NC or break) contact (see Operating Instructions Promag 55,
BA119D/06).
User interface:
BREAK CONTACT OPEN
BREAK CONTACT CLOSED
MAKE CONTACT OPEN
MAKE CONTACT CLOSED
SIMULATION SWITCH
POINT
(4741)
Use this function to activate simulation of the relay output.
Options:
OFF
ON
Factory setting:
OFF
!
Note!
• The "SIMULATION RELAY" message indicates that simulation is active.
• The measuring device continues to measure while simulation is in progress, i.e. the
actual measuring values are output correctly via the other outputs.
"
Caution!
The setting is not saved if the power supply fails.
Содержание Proline Promag 55
Страница 2: ...Device Functions Proline Promag 55 2 Endress Hauser ...
Страница 5: ...Device Functions Proline Promag 55 Contents Endress Hauser 5 ...
Страница 164: ...14 Index Device Functions Proline Promag 55 164 Endress Hauser ...
Страница 166: ...www endress com worldwide BA120D 06 en 10 09 71104957 FM SGML6 0 ...