![HART Proline Promag 55 Скачать руководство пользователя страница 122](http://html1.mh-extra.com/html/hart/proline-promag-55/proline-promag-55_manual_601405122.webp)
9 Block BASIC FUNCTION
Device Functions Proline Promag 55
122
Hauser
9.2.4
Function group ADJUSTMENT
BASIC FUNCTION
G
⇒
HART
GAA
⇓
PROCESS PARAMETER
GIA
⇒
CONFIGURATION
640
⇓
EPD PARAMETER
642
⇓
ECC PARAMETER
644
⇓
ADJUSTMENT
648
Function description
BASIC FUNCTION
➞
PROCESS PARAMETER
➞
ADJUSTMENT
EPD ADJUSTMENT
(6481)
Use this function to activate the EPD adjustment for an empty or full measuring tube.
!
Note!
A detailed description and other helpful hints for the empty pipe/full pipe adjustment
procedure can be found on Page 118.
Options:
OFF
FULL PIPE ADJUST
EMPTY PIPE ADJUST
Factory setting:
OFF
Procedure for EPD empty pipe / full pipe adjustment
1.
Empty the piping. In case of an EPD adjustment, the wall of the measuring tube
should be wetted with fluid.
2.
Start empty pipe adjustment: Select "EMPTY PIPE ADJUST" and press
F
to confirm.
3.
After empty pipe adjustment, fill the piping with fluid.
4.
Start full pipe adjustment: Select "FULL PIPE ADJUST" and press
F
to confirm.
5.
Having completed the adjustment, select the setting "OFF" and exit the function by
pressing
F
.
6.
Now select the EMPTY PIPE DETECTION function (s. Page 118). Switch on the
empty pipe detection by selecting ON STANDARD and press
F
to confirm.
"
Caution!
The adjustment coefficients must be valid before you can activate the EPD function. If
adjustment is incorrect the following messages might appear on the display:
– FULL = EMPTY
The adjustment values for empty pipe and full pipe are identical. In cases of this nature
you
must
repeat empty pipe or full pipe adjustment
again
!
– ADJUSTMENT NOT OK
Adjustment is not possible because the fluid’s conductivity is out of range.
Содержание Proline Promag 55
Страница 2: ...Device Functions Proline Promag 55 2 Endress Hauser ...
Страница 5: ...Device Functions Proline Promag 55 Contents Endress Hauser 5 ...
Страница 164: ...14 Index Device Functions Proline Promag 55 164 Endress Hauser ...
Страница 166: ...www endress com worldwide BA120D 06 en 10 09 71104957 FM SGML6 0 ...