9 Block BASIC FUNCTION
Device Functions Proline Promag 55
118
Hauser
9.2.2
Function group EPD PARAMETER
BASIC FUNCTION
G
⇒
HART
GAA
⇓
PROCESS PARAMETER
GIA
⇒
CONFIGURATION
640
⇓
EPD PARAMETER
642
Function description
BASIC FUNCTION
➞
PROCESS PARAMETER
➞
EPD PARAMETER
EMPTY PIPE DETECTION
(6420)
Flow cannot be measured correctly unless the measuring tube is completely full. This
status can be monitored at all times with the Empty Pipe Detection function. To do this,
the empty pipe detection (EPD, by means of an EPD electrode) can be activated in this
function:
Options:
OFF
ON STANDARD
Factory setting:
OFF
!
Note!
• The option ON STANDARD is not available unless the sensor is equipped with an EPD
electrode.
• The default setting for the EPD function when the device is delivered is OFF. The
function must be activated as required.
• The devices are already calibrated at the factory with water (approx. 500
μ
S/cm).
If the conductivity of certain fluids deviates from this reference, empty pipe/full pipe
adjustment must be performed again on site (see function EPD ADJUSTMENT (6481)
on Page 122).
• The adjustment coefficients must be valid before you can switch on the EPD function.
If these coefficients are not available, the function EPD ADJUSTMENT (6481) is
displayed (s. Page 122).
• If there are problems with the adjustment, the following error messages appear on the
screen:
– ADJUSTMENT FULL = EMPTY:
The adjustment values for empty pipe and full pipe are identical. In such instances,
empty pipe adjustment/full pipe adjustment
must
be carried out
again
.
– ADJUSTMENT NOT OK:
Adjustment is not possible as the fluid conductivity values are outside the permitted
range.
Notes on empty pipe detection (EPD)
• Flow cannot be measured correctly unless the measuring tube is completely full. This
status can be monitored at all times with the EPD function.
• An empty or partially filled pipe is a process error. A default factory setting defines that
a fault message is issued and that this process error has an effect on the outputs.
• The EPD process error can be output via the configurable relay or status outputs.
• Use the function ASSIGN PROCESS ERROR (8002) to define whether a notice or fault
message should be triggered (Page 144).
• A plausibility check of the adjustment values will only be executed by activating the
empty pipe detection. If an empty or full pipe adjustment is performed during the
empty pipe detection is active, the empty pipe detection has to be deactivated and
activated again, after finishing the adjustment, to start the plausibility check.
Response to partially filled pipes
If the EPD is switched on and responds to a partially filled or empty pipe, the fault
message "EMPTY PIPE" appears on the display. If the pipe is partially empty and the EPD
is
not
switched on, the response can vary in identically configured systems:
• Flow reading fluctuates
• Zero flow
• Excessively high flow values
Содержание Proline Promag 55
Страница 2: ...Device Functions Proline Promag 55 2 Endress Hauser ...
Страница 5: ...Device Functions Proline Promag 55 Contents Endress Hauser 5 ...
Страница 164: ...14 Index Device Functions Proline Promag 55 164 Endress Hauser ...
Страница 166: ...www endress com worldwide BA120D 06 en 10 09 71104957 FM SGML6 0 ...