8 Block INPUTS
Device Functions Proline Promag 55
110
Hauser
8.2.2
Function group OPERATION
INPUTS
F
⇒
STATUS INPUT
FAA
⇓
CURRENT INPUT
FCA
⇒
CONFIGURATION
520
⇓
OPERATION
524
Function description
INPUTS
➞
CURRENT INPUT
➞
OPERATION
ACTUAL CURRENT
(5240)
Use this function to view the actual value of the input current.
User interface:
0.0 to 25 mA
SIMULATION CURRENT
(5241)
Use this function to activate the simulation of the current input.
Options:
OFF
ON
Factory setting:
OFF
!
Note!
• An active simulation is displayed by the notice message "SIM. CURR. IN 1" (# 661).
• The value output for the simulation at the current input is defined in the function
VALUE SIMULATION CURRENT (5242).
• The measuring device remains fully operational during the simulation and the actual
measuring values are output correctly via the other outputs and the display.
"
Caution!
The setting is not saved if the power supply fails.
VALUE SIMULATION
CURRENT
(5242)
!
Note!
This function is only available if the function SIMULATION CURRENT (5241) is
switched on.
Use this function to specify a freely selectable value, e.g. 12 mA, which is to be simulated
at the current input. This value is used to test downstream devices and the flowmeter
itself.
User input:
0.00 to 25.00 mA
Factory setting:
0.00 mA or 4 mA (depending on the setting in function 5201).
"
Caution!
The setting is not saved if the power supply fails.
Содержание Proline Promag 55
Страница 2: ...Device Functions Proline Promag 55 2 Endress Hauser ...
Страница 5: ...Device Functions Proline Promag 55 Contents Endress Hauser 5 ...
Страница 164: ...14 Index Device Functions Proline Promag 55 164 Endress Hauser ...
Страница 166: ...www endress com worldwide BA120D 06 en 10 09 71104957 FM SGML6 0 ...