Device Functions Proline Promag 55
9 Block BASIC FUNCTION
Hauser
113
9.1
Group HART
9.1.1
Function group CONFIGURATION
BASIC FUNCTION
G
⇒
HART
GAA
⇒
CONFIGURATION
600
Function description
BASIC FUNCTION
➞
HART
➞
CONFIGURATION
TAG NAME
(6000)
Use this function to enter a tag name for the measuring device. You can edit and read this
tag name at the local display or via the HART protocol.
User input:
max. 8-character text, permissible: A–Z, 0–9, +, –, punctuation marks
Factory setting:
"_ _ _ _ _ _ _ _" (no text)
TAG DESCRIPTION
(6001)
Use this function to enter a tag description for the measuring device. You can edit and
read this tag description at the local display or via the HART protocol.
User input:
max. 16-character text, permissible: A–Z, 0–9, +, –, punctuation marks
Factory setting:
"_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _" (No text)
BUS ADDRESS
(6002)
Use this function to define the address for the exchange of data with the HART protocol.
User input:
0 to 15
Factory setting:
0
!
Note!
Addresses 1 to 15: a constant 4 mA current is applied.
HART PROTOCOL
(6003)
Use this function to display if the HART protocol is active.
User interface:
OFF = HART protocol not active
ON = HART protocol active
!
Note!
The HART protocol can be activated with the selection 4–20 mA HART or
4–20 mA (25 mA) HART in the CURRENT SPAN function (see Page 58).
WRITE PROTECTION
(6004)
Use this function to check whether the measuring device can be write-accessed.
User interface:
OFF (Data exchange is possible)
ON (Data exchange is disabled)
Factory setting:
OFF
!
Note!
Write protection is activated and deactivated by means of a jumper on the I/O module
(see Operating Instructions Promag 55, BA119D/06).
Содержание Proline Promag 55
Страница 2: ...Device Functions Proline Promag 55 2 Endress Hauser ...
Страница 5: ...Device Functions Proline Promag 55 Contents Endress Hauser 5 ...
Страница 164: ...14 Index Device Functions Proline Promag 55 164 Endress Hauser ...
Страница 166: ...www endress com worldwide BA120D 06 en 10 09 71104957 FM SGML6 0 ...