4 Block QUICK SETUP
Device Functions Proline Promag 55
26
Hauser
!
Note!
In the case of measuring devices without a local display, the individual parameters and functions
must be configured via the configuration program, e.g. FieldCare. If the measuring device is
equipped with a local display, all the important device parameters for standard operation can be
configured quickly and easily by means of the "Commissioning" Quick Setup menu.
• The display returns to the cell SETUP COMMISSIONING (1002) if you press the ESC key
combination during parameter interrogation. The stored parameters remain valid.
• The "Commissioning" Quick Setup must be carried out before one of the Quick Setups explained
below is run.
m
The DELIVERY SETTINGS option sets every selected unit to the factory setting.
The ACTUAL SETTINGS option accepts the units you previously configured.
n
Only units not yet configured in the current Setup are offered for selection in each cycle.
The unit for mass, volume and corrected volume is derived from the corresponding flow unit.
o
The "YES" option remains visible until all the units have been configured.
"NO" is the only option displayed when no further units are available.
p
Only the outputs not yet configured in the current Setup are offered for selection in
each cycle.
q
The "YES" option remains visible until all the outputs have been parameterized.
"NO" is the only option displayed when no further outputs are available.
r
The "automatic parameterization of the display" option contains the following
basic settings/factory settings:
YES: Main line = Mass flow; Additional line = Totalizer 1;
Information line = Operating/system conditions
NO: The existing (selected) settings remain.
Содержание Proline Promag 55
Страница 2: ...Device Functions Proline Promag 55 2 Endress Hauser ...
Страница 5: ...Device Functions Proline Promag 55 Contents Endress Hauser 5 ...
Страница 164: ...14 Index Device Functions Proline Promag 55 164 Endress Hauser ...
Страница 166: ...www endress com worldwide BA120D 06 en 10 09 71104957 FM SGML6 0 ...