888-2406-002
6-37
WARNING: Disconnect primary power prior to servicing.
Troubleshooting
Table 6-5 Z2 or Z2R PS Controller Related Faults
ABBREVIATION
COMMENT
ACTION
PSC# +20V
+20V DC supply to PSC failed
Shut PS OFF and discharge
PS#_DSCHG
Discharge circuit failed which means
the PS will not discharge. If discharge
resistor is open, a PS#_START fault
will prevent the transmitter from
being turned on again. The same
resistor is used for both purposes.
Transmitter is shut OFF
PS#_START
Not able to soft start. Could be an
SCR problem or open soft start/
discharge resistor (Mounted on top of
each transformer).
Shut PS OFF and discharge
PS#_HS_TEMP
SCR heat sink temperature overload
Shut PS OFF and discharge
PS#_PHS_LS
Transformer primary phase loss or
severe imbalance
Transmitter will Mute for 20
seconds, then try to turn on again.
This will be repeated until
successful.
PS#_CONFIG
Power supply #n has cable
configuration fault
Mute
PS#_JUMP
Upper or lower tap not available once
current tap failed
Shut power supply off and discharge
PS#_TAP1
Tap 1 failed. One or more of the
secondary SCRs for the 48V tap have
failed on the designated Power
Supply.
Tap1 fault indication. PSC will
automatically switch to Tap2 if it is
not faulted. If Tap2 is faulted, off
shut Tx off with PS#_JUMP fault.
PS#_TAP2
Tap 2 failed. One or more of the
secondary SCRs for the 50V tap have
failed on the designated Power
Supply.
Tap2 fault indication. PSC will
automatically switch to Tap1 if it is
not faulted. If Tap1 is faulted off,
switch to Tap3. If Tap3 is faulted off,
shut TX off with PS#_JUMP fault.
PS#_TAP3
Tap 3 failed. One or more of the
secondary SCRs for the 52V tap have
failed on the designated Power
Supply.
Tap3 fault indication. PSC will
automatically switch to Tap2 if it is
not faulted. If Tap2 is faulted off,
switch to Tap4. If Tap4 is faulted off,
shut TX off with PS#_JUMP fault.
PS#_TAP4
Tap 4 failed. One or more of the
secondary SCRs for the 54V tap have
failed on the designated Power
Supply.
Tap4 fault indication. PSC will
automatically switch to Tap3 if it is
not faulted. If Tap3 is faulted off,
shut TX off with PS#_JUMP fault.
PS#_COMM
PS Controller not able to
communicate with the Master
Fault indication. No transmitter
action taken.
NOTE: # is the number of the power supply 1 or 2
Содержание Platinum Z2 CD
Страница 4: ...888 2406 002 WARNING Disconnect primary power prior to servicing ...
Страница 6: ...888 2406 002 WARNING Disconnect primary power prior to servicing ...
Страница 8: ...888 2406 002 WARNING Disconnect primary power prior to servicing ...
Страница 10: ...888 2406 002 WARNING Disconnect primary power prior to servicing ...
Страница 20: ...1 6 888 2406 002 WARNING Disconnect primary power prior to servicing Introduction Specifications ...
Страница 70: ...3 14 888 2406 002 WARNING Disconnect primary power prior to servicing Operator Guide ...
Страница 130: ...4 60 888 2406 002 WARNING Disconnect primary power prior to servicing Overall System Theory ...
Страница 156: ...5 26 888 2406 002 WARNING Disconnect primary power prior to servicing Maintenance and Alignment ...
Страница 194: ...6 38 888 2406 002 WARNING Disconnect primary power prior to servicing Troubleshooting ...
Страница 196: ...7 2 888 2406 002 WARNING Disconnect primary power prior to servicing Parts List ...