Chapter 7 Troubleshooting
H
- 120 -
Over speed
(Alarm clear: not available)
●
Description
The alarm occurs when the motor axis speed exceeds the maximum rotation speed +100 rpm for 0.5 s
or longer. It can be reset by shutting down the power and turning it on again.
●
Diagnostic tips
(1) Alarm occurs when the control circuit power is turned on:
◆
Cause 1: Failure of the control circuit of the HA-680 driver
⇒
Remedy: Contact Harmonic Drive Systems,Inc. (Replace the HA-680 driver)
(2) Alarm occurs when you enter a rotation command and the actuator rotates at high
speed:
◆
Cause 1: (Position control) “Command pulse frequency” is too large.
⇒
Remedy: Lower the “command pulse frequency” in the host device.
Set it to a frequency lower than the maximum rotation speed (r/min) of the
actuator.
◆
Cause 2: (Speed control) “Speed command input voltage” is too high.
⇒
Remedy: Lower the “speed command output voltage” in the host device.
◆
Cause 3: “Speed command input factor” is too high.
⇒
Remedy: Lower [30: Speed command input factor] in [Parameter].
◆
Cause 4: Wrong setting of “analog voltage command gain”
⇒
Remedy: Change [30: Speed command input factor] in [Parameter].
◆
Cause 5: A significant overshoot due to insufficient gain adjustment
⇒
Remedy: Adjust gains in [parameter]
→
[01: Speed loop proportional gain], [02: speed
loop integral gain] and [03: Speed loop derivative gain] proportional
according to the load.
◆
Cause 6: Wrong connection of the motor or encoder
⇒
Remedy: Perform connection properly by referring to “Chapter 3 Installing HA-680
driver” in this manual.