Chapter 6 Setting up parameters
-
88
-
15: Control input filter time constant
(position / speed / torque)
●
Function
This function sets the time constant of the soft low-pass filter applied to the signals at the control input
terminal other than forward rotation/reverse rotation command pulses.
If it is used in an environment where there is external high-frequency noise, set the value so that the
control input signal is not easily affected by the noise.
●
Setting
unit
Lower limit
Upper limit
Default
ms
0
99
0
16: Speed limiting
(position / speed)
●
Function
This function sets the motor rotation speed at which the speed limit becomes effective when the speed
limit function is assigned to the signal input in the parameter “13: Input pin logical setting.”
A value from [1] to [Motor maximum rotation speed] can be entered.
●
Setting
unit
Lower limit
Upper limit
Default
r/min
0
Motor maximum
rotation speed
Motor maximum
rotation speed
Note 1: Motor rotation speed = Actuator rotation speed x reduction ratio
Note 2: When operation continues with the motor rotation speed limited during position control, an error
counter overflow alarm occurs.
This parameter cannot be set for torque control. The upper limit value of the
parameter is “motor maximum rotation speed.” When the load of the actuator is
small (including no load), it may rotate at the maximum rotation speed
instantaneously.
WARNING