HARDY MANUFACTURING CO., INC (MODEL LC300, LC500 & LC2500)
PAGE 54
8-7
Honeywell Aqua Stat Replacement Instructions (continued)
Step #
Operation Description
Visual Aids/Comments
6
Open the heater tank drain valves and allow the furnace
tank to drain until the tank water level is below the
thermostat level.
7
Using an adjustable wrench remove the well fitting from
the rear of the furnace.
8
Apply pipe joint compound to the threads of the new
well fitting and then screw the fitting into the rear of the
furnace. Use an adjustable wrench to tighten the fitting.
9
Remove the cover from the new thermostat. Loosen the
two screws on the thermostat clamp. Make sure the
clamp is loose enough to slide over the notch in the well
fitting.
10
Slide the bulb into the well fitting. Position the
thermostat so that the thermostat well hole is centered
over the well, the thermostat is perpendicular to the
ground and the clamp is engaged in the groove of the
well fitting. Tighten the two well clamp screws. Do not
over tighten the clamp screws.
Open these valves
!
Hazardous Voltage! Disconnect Power to
Heater prior to performing this
maintenance operation.