HARDY MANUFACTURING CO., INC (MODEL LC300, LC500 & LC2500)
PAGE 24
4-1
Connection to Central Unit with Existing Blower Relay (continued)
This unit must be wired by a qualified electrician in accordance with the National
Electrical Code.
At the air handler inside, find the red wire going from the air handler control wiring to
the original wall thermostat. Cut this wire and connect the end that is going to the wall
thermostat to terminal # 2 on the new relay. The end of the red wire that is still
connected to the control wiring of the air handler will need to be connected to terminal
# 1 along with the new red wire that is going to the new heat only wall thermostat.
Locate the Green wire going from the central air handler control wiring to the original
wall thermostat. Cut this wire. Connect the end of the green wire that is going to the
original wall thermostat to terminal #5 of the new relay. Connect the end of the green
wire that is still connected to the central air handler control wiring to terminal #4.
Connect the white wire going to the new heat only thermostat to the red wire going
outside to the wood heater. Take the green wire that is going outside to the Hardy
Hydronic Heater and along with a short jumper wire (appx. 3” - 4” long) connect to
terminal #7 on the new relay that was added to the air handler. Connect the other end
of this jumper wire to terminal #6 of the relay.
Locate the low voltage transformer that is providing you with 24 volt power. Find the
common lead of this transformer and connect a wire to this lead and to terminal #8 of
the new relay along with the white wire going outside to the Hardy Hydronic Heater .
If all connections are made properly and the water in the Hardy Hydronic Heater is hot,
the unit should be ready for operation.
NOTE: This is a general diagram. You may have to make various changes according
to how your unit is wired. Insure that the compressor on a heat pump or A/C unit does
not run when the wood system is running. Insure that the gas burner, oil burner, or
electric elements do not come on when the wood system is running. Insure that only
one speed of the blower motor can be energized at one time. If more than one speed
is energized at the same time, the blower motor will burn out. Insure that the volt amp
rating of the existing 24 volt transformer is not exceeded when the relays in the Hardy
Hydronic Heater system are energized.
Содержание LC300
Страница 2: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 10: ... MODEL LC300 LC500 LC2500 viii THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 70: ......
Страница 71: ......
Страница 72: ......