K-BUS
KNX/EIB 3.5/5.0/10.1 inch Touch Panel Plus
86
○
R
7.3.6 “Air conditioner”Communication Object
Figure 7.3_6 “Air conditioner”Communication
(
VRV Unit _1byte
)
Figure 7.3_6 “Air conditioner”Communication Object
(
VRV Unit _1bit
)
Figure 7.3_6 “Air conditioner”Communication Object
(
IR Split Unit
)
S/N
Function
Communication
Object Name
Type
Attribut
e
DPT
5
Power on/off
Page x-AC
1bit
C,T
1.001 switch
5
IR Split unit command
Page x-AC
1byte
C,T
17.001 scene number
Power on/off: The communication object is visible in VRV air-conditioner mode, which is used to
send messages of air-conditioner on/off.
IR Split unit command: The communication object is visible in split infrared mode, which is used to
send messages of air-conditioner control. The parameter can set controlling telegram 1~64, while the
actual message value on the BUS is corresponding to 0~63.
6
Status of Power
Page x-AC
1bit
C,W,T,U
1.001 switch
The communication object is visible in VRV air-conditioner mode, which is used to receive
feedback of air-conditioner on/off status.
7
Control mode
Page x-AC
1byte
C,T
5.010 counter pluses
7
Heating mode
Page x-AC
1bit
C,W,T,U
1.001 switch
1byte: The communication object will be visible when it’s in VRV AC mode & the mode type is
1byte, which is used to send controlling message of all AC mode.
1bit: The communication object will be visible when it’s in VRV AC mode & the mode type is 1bit,