7.3.5 “HVAC”Communication Object
Figure 7.3_5 “HVAC”Communication Object
S/N
Function
Communication Object Name
Type
Attribute
DPT
5
Humidity
Page x- HVAC Input
2byte
C,W,T,U
9.007 humidity
The communication object is used to receive humidity measurement value sent by the humidity sensor
from the BUS. The range
:
0~100%
6
External temperature
sensor
Page x- HVAC Input
2byte
C,W,T,U
9.001 temperature
The communication object is used to receive temperature measurement value sent by the temperature
sensor from the BUS. Range: -50~99.8
℃
.
7
Setpoint adjustment
Page x- HVAC Input
2byte
C,W
9.001 temperature
When the set temperature is opposite adjustment, the adjustment of set temperature is only applied for the
mode itself under protection mode.
Opposite changes of temperature adjustment of other mode could be applied to set temperature of all
modes(except the protection mode).
Under the circumstance of definite set temperature, the adjustment of set temperature is only used for all