K-BUS
KNX/EIB 3.5/5.0/10.1 inch Touch Panel Plus
90
○
R
B: Blue dimming value.
5
RGBW dimming value
Page x-RGB Dimming
6byte
C, T
251.600 RGB value 4x(0..255)
This communication object is visible when RGBW-1x6byte is selected for the RGB type and is used
to send the brightness value of the RGBW four-color lamp.
6-byte RGBW dimming object data type encoding: U8 U8 U8 U8 R8 R4 B4
,
details are as follows
:
6
MSB
5
4
3
2
1
LSB
R
G
B
W
Reserve
r r r r mR mG mB mW
UUUUUUUU
UUUUUUUU
UUUUUUUU
UUUUUUUU
00000000
0000BBBB
R:
Red dimming value;
G: Green
dimming value
;
B: Blue
dimming value
;
W: White
dimming value
;
mR: Determine whether the red dimming value is valid, 0=Invalid, 1=Effective
;
mG: Determine whether the Green dimming value is valid, 0=Invalid, 1=Effective
;
mB: Determine whether the Blue dimming value is valid, 0=Invalid, 1=Effective
;
mW: Determine whether the White dimming value is valid, 0=Invalid, 1=Effective
;
Form 7.3_8 “RGB dimming”communication object form
7.3.9 “Floor heating”Communication object
Figure 7.3_9 “Floor heating”communication object
No.
Function
Communication object name
Type
Attribute DPT
5
Heating on/off
Page x-Floor heating
1bit
C,W,T,U
1.001 switch
This communication object is used to send floor heating control commands. It can also receive floor heating
feedback status feedback. The switch status corresponding to the packet value is specifically set by parameters.
6
Setpoint
Page x-Floor heating
2byte
C,W,T,U
9.001 temperature
This communication object is used to send the temperature setpoint to the bus. Feedback temperature settings can
also be received. Range: 5~40°C
7
External
temperature
sensor
Page x-Floor heating
2byte
C,W,T,U
9.001 temperature
This communication object is visible when an external sensor is selected for temperature reference and is used to
receive the temperature measurement sent from the temperature sensor on the bus. Range: -50~99.8°C
8
En./Dis. timer
Page x-Floor heating
1bit
C,W
1.003 enable
This communication object is used to disable/enable warming of the floor. The disabled/enabled message values are
specifically defined by parameters.
9
Scene
Page x-Floor heating
1byte
C,W
17.001 scene number
This communication object is used to invoke floor heating control. The parameter setting is 1~64, and the actual