K-BUS
KNX/EIB 3.5/5.0/10.1 inch Touch Panel Plus
73
○
R
6.8.2 “Gate forwarding”function parameter
Fig.6.8_3“Logic function -- Gate forwarding”parameter setting window
Parameter“Object type of Input/Output”
This parameter is used to set the data type of the input/output object.The options:
1bit
4bit
1byte
Parameter“Scene NO. Of Gate after startup (1..64, 0=inactive)”
This parameter is used to set the default activated Scene No. Of the logic Gate after device startup.This
scene should be configured in the relevant parameter.
The options:1..64,0
=
inactive
Parameter“z->Gate trigger scene NO. is(1..64,0=inactive)” (z:1~8)
This parameter is used to set the gate triggered scene No..Each logic can support Maximum 8 scenes.The
options:
:
1..64, 0=inactive.
Parameter“Input A/B/C/D send on”
This parameter is used to set the output after the input getting through logic gate
Output A
Output B
..
Output B,C,D