K-BUS
KNX/EIB 3.5/5.0/10.1 inch Touch Panel Plus
56
○
R
——Parameter “Delay between fan speed switch [0..100]*50ms”
While the define turns to Delay, the time can be considered based on technical characteristics of the fan.
Options: 0...100
When the wind speed is switched, the wind speed is turned off firstly, and then the wind speed is re-opened
after the delay time to send the telegram to the bus.
Status feedback for fan speed
The following parameters are visible when the wind speed object is "1byte", to set the status value for
fan speed off/low/medium/high.
——Parameter “Status value for fan speed off/low/medium/high”
This parameter is used to set the status value for fan speed off/low/medium/high. The touch panel will
update the Icon status of the fan speed according to the received value. Options: 0-255
Parameter “Heat Recovery function”
This parameter is used to set whether to enable Heat recovery function. Options:
No
Disable=0/Enable=1
Disable=1/Enable=0
If the last two options are selected, the Heat Recovery is enabled by default, that is, it is enable once boots.
While “No” is selected, the heat recovery is not controllable
Parameter “Filter timer counter”
This parameter is used to set whether to enable the filter timer counter function. Options:
Disable
Enable
While it is “Enable”, the next parameter is visible
——Parameter “Evaluation time [100..10000]*h”
This parameter is used to set the evaluation time of filter. Options: 100..10000
If longer than the set time, the filter will send out a warning of prompting to clean the filter.
The Evaluation time can be reset via object “Filter timer reset, In”.
The Evaluation time can be counted by the object "Filter timer counter, In/Out" and the timing is changed will
send to the bus once 1h.
Parameter “Auto. operation function”
This parameter is used to enable Auto. Operation function. Options:
Disable
Enable