K-BUS
KNX/EIB 3.5/5.0/10.1 inch Touch Panel Plus
65
○
R
——Parameter“Reduced heating during night mode [0..10]
℃
”
——Parameter“Increased cooling during night mode [0..10]
℃
”
This parameter is used to set the temperature setpoint under night mode.Options:0...10 [
℃
]
Heating
:
The temperature setpoint in the night mode becomes the value,which the basic value reduce the
set value here.
Cooling
:
The temperature setpoint in the night mode becomes the value,which the basic value plus the set
value here.
——Parameter“Actual Temp. threshold in frost protection[5..10]
℃
”(for heating)
This parameter is used to set heating function temperature setpoint under frost protection
mode.Options:5...10 [
℃
]
When the room temperature is lower than the set value here,the controller will send a control telegram to the
bus to active the relevant heating actuator to avoid low temperature in the room.
——Parameter“Actual Temp. threshold in heat protection[30..40]
℃
”(for cooling)
This parameter is used to set cooling function temperature setpoint under heat protection
mode.Options:30...40 [
℃
]
When the room temperature is higher than the set value here,the controller will send a control telegram to
the bus to active the relevant cooling actuator to avoid high temperature in the room.
Enable “Absolute”,the following parameters are available,which are used to set the temperature setpoint
under Absolute operation mode.
——Parameter“Setpoint Temp. in comfort mode [5..40]
℃
”
——Parameter“Setpoint Temp. in standby mode [5..40]
℃
”
——Parameter“Setpoint Temp. in night mode [5..40]
℃
”
——Parameter“Setpoint Temp. in frost protection mode [5..40]
℃
”(for heating)
——Parameter“Setpoint Temp. in heat proection mode [5..40]
℃
”(for cooling)
This parameters is used to set the temperature setpoint of each mode.Options:5-40
℃