K-BUS
KNX/EIB 3.5/5.0/10.1 inch Touch Panel Plus
63
○
R
Parameter “Controller-General for HVAC function”
This parameter is used for enable and disable the HVAC in the page function.Options:
Disable
Enable
If the HVAC function is not used on the page function,choose
“Disable”.
Parameter “Send control value on change by [0..100, 0=inactive]%”
This parameter is used to set how many value changed can the telegram be sent to the bus. Available from
0..100
,
0 means no telegram sent to bus.
Parameter“Cyclically send control value [0..255]min”
This parameter is used to set the time period of cyclically sending control value to the bus.Options:0..255
Parameter“Controller status after restart”
This parameter is used to set the operation mode when the device is rebooted.Options:
Standby mode
Comfort mode
Night mode
Frost/heat protection
Parameter“Extended comfort mode [0..255, 0=inactive]*min”
This parameter is used to set the delay time of the confirm mode.Options: 0...1-255 [min.]
1) When the setting value is “0”,the comfort mode is disabled.
2) When the setting value is from 1-255 and the room mode is switching from night to comfort,the comfort
mode is enabled.
3) The comfort mode will be switch to night mode automatically when the delay time is over.
4) This parameter is only for the mode switch between comfort and night.
Parameter“HVAC Control mode”
This parameter is used to set the HVAC control mode,options:
Heating
Cooling
Heating and Cooling
Heating and cooling
:
Both heating and cooling can be fulfilled.The following parameter is available.