K-BUS
KNX/EIB 3.5/5.0/10.1 inch Touch Panel Plus
76
○
R
6.8.4 “Format convert”function parameter
Fig.6.8_5 parameter setting window“Logic function -- Format convert”
Parameter“Function”
This parameter is used to set the data convert format.The options:
2x1bit-->1x2bit
8x1bit-->1x1byte
1x1byte-->1x2byte
2x1byte-->1x2byte
2x2byte-->1x4byte
1x1byte-->8x1bit
1x2byte-->2x1byte
1x4byte-->2x2byte
1x3byte-->3x1byte
3x1byte-->1x3byte
Parameter“Output send when”
This parameter is used to set the condition of sending the logic operation result.The options:
Receiving a new telegram
Every change of output object
Receiving a new telegram:when a new logic input value is received,the logic operation result will always be
sent to the bus.
Every change of output object:when the logic operation result changes,it will be sent to the bus.
Note:
Although the logic operation result is not changed when doing the first logic operation,it also will be
sent to the bus.