K-BUS
KNX/EIB 3.5/5.0/10.1 inch Touch Panel Plus
72
○
R
Parameter“Default value”
This parameter is used to set the initial input value of the logic input x.The options:
0
1
Parameter“Result is inverted”
This parameter is used to set whether to invert the logic operation result.The options:
No
Yes
No:Output directly.
Yes:Output the inverted output.
Parameter“Read input object value after bus voltage recovery”
This parameter is used to set whether to send read request to the logic input object after the bus recovered
or programmed.
No
Yes
Parameter“Output send when”
This parameter is used to set the condition of sending the logic operation result.
Receiving a new telegram
Every change of output object
Receiving a new telegram:when a new logic input value is received,the logic operation result will always be
sent to the bus.
Every change of output object:when the logic operation result changes,it will be sent to the bus.
Note:
Although the logic operation result is not changed when doing the first logic operation,it also will be
sent to the bus.
Parameter“Send delay time”
Base:
None
0.1s
1s
...
10s
25s
Factor:
1..255
This parameter is used to set the delay time of the logic operation result sending to the bus.
Delay=Base x Factor,for example,when the base is “None”,there is no delay.