corresponding message value is 0~63.
Form 7.3_9 “Floor heating”Communication object form
7.3.10 “Ventilation System”Communication Object
Figure 7.3_10 “Ventilation system”Communication Form
Number
Function
Communication object name
Type
Attribute DPT
5
External temperature sensor
Page x-Ventilation
2byte
C,W,T,U 9.001 temperature
This communication object is visible when an external sensor is selected for temperature reference and is used to
receive the temperature measurement sent from the temperature sensor on the bus. Range: -50~99.8°C
6
Automatic function, In/Out
Page x-Ventilation
1bit
C,W,T,U 1.003 enable
This communication object is used to enable automatic operation of fresh air.
After the bus is reset or programmed, automatic operation is disabled by default. Shutdown, manual adjustment of
wind speed, scene can exit the automatic operation.
The auto-enable/disable message value is defined by parameters.
7
Fan speed, In
Page x-Ventilation
1byte
C,W,T,U 5.010 counter pulses
This communication object is visible when the wind speed type is "1byte" and is used to receive the status feedback
of wind speed. The specific message value corresponding to each wind speed is defined by parameters.
8
Fan speed, Out
Page x-Ventilation
1byte
C,T
5.010 counter pulses
The communication object is visible when the wind speed type is "1byte" and is used to send a message controlling
the wind speed to the bus. The specific message value corresponding to each wind speed is defined by parameters.
7
Fan Speed No.1 1Bit, In/Out
Page x-Ventilation
1bit
C,W,T,U 1.001 switch
8
Fan Speed No.2 1Bit, In/Out
Page x-Ventilation
1bit
C,W,T,U 1.001 switch
9
Fan Speed No.3 1Bit, In/Out
Page x-Ventilation
1bit
C,W,T,U 1.001 switch
These three communication objects are visible when the wind speed type is “1 bit”, and the wind speed is controlled
by three objects at the same time. The specific message value corresponding to each wind speed is defined by
parameters. Can receive status feedback, but the feedback value also needs to correspond with the parameter definition
value to update the on-screen display.
10
Heat Recovery, In/Out
Page x-Ventilation
1bit
C,W,T,U 1.001 switch
The communication object is used to send a control command to open/close the hot air exchange, and it can also