![GST GST200 Скачать руководство пользователя страница 48](http://html1.mh-extra.com/html/gst/gst200/gst200_installation-and-operation-manual_2275587048.webp)
GST200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
The Intelligent Solution
Page 45
Chapter 8 Maintenance
The FACP shall only be repaired by specially trained GST technical service personnel.
Please disconnect the power before repair!
8.1 Replacing the Battery
Type of battery: Sealed lead-acid battery
Recommended period for replacing the battery: 5 years (25
℃
)
Recommended manufacturer and model: Yuasa/NP17-12I
Disposal of used batteries: Please properly dispose the used batteries according to
your local rules and regulations.
NOTE:
RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT
TYPE.
8.2 Replacing the Fuses
Table 8-1
Location Mark
Rated
Value
Power filter F7.820.323
F1
2A Delay
Power board F7.820. 829
F1, F2
5A
Loop interface board F7.820. 828
F1, F2, F3
2A
8.3 Troubleshooter