GST200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
The Intelligent Solution
Page 18
connection. The maximum current of the circuit depends on the number of fire
supervisory device. Do not overload.
Connection of Class A Loop
A Class A loop is shown in Fig. 4-7.
LOOP OUT
(XT4)
LOOP IN
(XT2)
Fig. 4-7
Note: If more than 32 devices are connected to the loop, loop isolators shall be
used and each loop isolator shall not cover more than 32 detectors.
Connection of Communication Loop
Fig. 4-8
4.5 Connection Inspection and Device Registration
4.5.1 Connection
Inspection
Check the circuit connected with the FACP. Measure the insulation resistance between
loops and between loops and ground, which should be more than 20M
Ω
. Measure the
load of detection loops, which should be more than 1k
Ω
. The resistance between cables
of FIRE ALARM OUTPUT, SOUNDER CIRCUIT OUTPUT and F.P.E. OUTPUT should
be equal to the end-of-line resistance.
Addressable
field devices
Loop
Isolator
Addressable
field devices
Loop
Isolator
Maximum 32 FACPs
Network
(XT11)
Maximum 10 Repeater Panels
F
ACP
F
ACP
Re
Re
p
p
Repeater
(XT12)
eate
r Pan
e
l
eate
r Pan
e
l