![GST GST200 Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/gst/gst200/gst200_installation-and-operation-manual_2275587014.webp)
GST200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
The Intelligent Solution
Page 11
communication port, connecting with network cards to realize networking among
GST series FACPs, to form urban fire alarm supervisory network through public
telephone network and to fulfill graphic supervision by connecting with GstGMC2.0
Graphic Monitor Center (GMC) system at the control center of buildings. The FACP
monitors the running of network cards in real time so that the card can work after
inserted.
GST200 provides two kinds of network cards: Local Network Card (RS-485 card)
and Monitor & Control Card (RS-232 card). Their structures are shown in Fig. 3-5.
Fig. 3-5
Description:
1 20P data cable connecting with main board.
2 Red LED, which lights on receiving signals.
3 Green LED, which lights on sending signals.
4 RS-485 network communication cable (A and B).
5 20P data cable connecting with main board.
6 Standard RS-232 interface connecting with GMC.
Note: You need to include a RS-232 card in your first order of GST200. Only with
this card, device definition and C&E equations can be downloaded from PC.
3.3 Periphery Devices
3.3.1
A Series of Intelligent Fire Detectors
GST200 can connect with a series of fire detectors, such as I-9102, I-9103, and I-9105R.
The detectors mounted in the protected area transmit monitoring message to the FACP
through Class A loop. Every detector has its own address with which the FACP can
supervise the information of alarm, fault, and normal status of the detectors.
3.3.2 Modules
GST200 can connect with I-9300 Addressable Input Module and I-9301 Addressable
Single I/O Module. I-9300 module is used for receiving normally open digital signal from
Содержание GST200