![GST GST200 Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/gst/gst200/gst200_installation-and-operation-manual_2275587022.webp)
GST200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
The Intelligent Solution
Page 19
4.5.2
Device Registration
Press
SYSTEM
and input commission password. Then press
ENTER
to go to system
setting menu. Then press
ESC
to exit system setting menu, the system enters
commission state (there will be a “-“ at the right bottom of the screen). Press
SELF
TEST
, the FACP will register the devices automatically. Please check if the number of
devices, programming, and operation state is in compliance with the project design and
remove any problems.
4.6 Device Definition
Please define devices and C&E equations by the software GstDef2.0 Defining Tool
through a PC, and download the definitions to the FACP. Refer to
GstDef2.0 Defining
Tool User’s Manual
for detailed operation.
4.7 Field Device Commission
After connection, definition and download of device and C&E equations, you can power
up the FACP and start commission. The following steps are for reference.
1
Complete the labels of ZCP.
2
Test all the detectors and make sure their positions are correct.
3
Check all device definition, and modify improper part.
4
Check all C&E equations, modify improper parts, and test automatic activation by
C&E equation.
Содержание GST200