GST200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
The Intelligent Solution
Page 23
Keypad fault: The panel reports keypad fault if its keypad circuit is in fault:
¾
It
lights
the
COMMON FAULT
and
SYSTEM FAULT
LED.
¾
The LCD displays “Key fault”.
¾
The panel generates continuous alarm sound.
¾
Fault relay outputs.
¾
The keypad cannot be used.
¾
The panel can monitor fire alarm.
¾
The panel can reset automatically after the fault is removed.
Field device fault: If there is trouble with one of the field devices, the panel reports
fault with it, and
¾
The panel lights the
COMMON FAULT
LED.
¾
The corresponding ZCP LED flashes.
¾
The panel generates fault sound.
¾
Fault relay outputs.
¾
The LCD displays the fault message. The fault screen is as in Fig. 5-5 in zone
display mode, and as in Fig. 5-6 in loop display mode.
Fig. 5-5
001 0f 002 FAULT10:18
Zone:003-floor3
Office3
¾
001 0f 002 FAULT10: 18 // There are two zones reporting fault, and this is the
first fault message.
¾
Zone:003-floor3 // The number description of the zone with fault message.
¾
Office3 // Description of the device with the fault.
001 0f 004FAULT10:18
Zone:003-011Optical
Fig. 5-6