GST200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
The Intelligent Solution
Page 24
¾
001 0f 004 FAULT10:18 // There are four devices reporting fault, and this is the
first fault message.
¾
Zone:003-011Optical // The number the zone with the fault message, the
address and type of the device with the fault message.
5.3.2
Disposal of Fault Message
There are two kinds of fault message. One is system fault, like AC fault, battery fault,
and loop fault. The other is field device fault, like fault with detectors and modules etc.
If the system is powered by battery for longer time than its capacity, the panel will
shut down to protect the battery. Please charge the battery in time to avoid any
possible damage to it.
If it is system fault, please check and repair in time. If the panel needs to be shut
down, please make detailed notes.
If it is field device fault, please repair it in time. You can disable it if the fault can’t be
cleared for some reason, and enable it when the fault is removed.
5.4 Rules for Message Display
If there are multiple messages in the system, they will be displayed in the following order:
fire alarm, action, fault, start, disable.
1 The earliest fire alarm is displayed in priority. The latest action, fault, disabled
message is displayed in priority.
2
There are zone and loop display modes for fire alarm, fault, and disabled messages.
And start and action only has loop display mode.
3 In any display mode, the system will return to displaying of the highest priority if
there is no operation within 20s (15s
~
30s).
5.5 Rules for Sound Indication
The FACP will sound to indicate fire alarm or fault messages.
The FACP gives fast “tick” sound when fire alarm occurs.
The FACP gives action sound when any device is activated.
¾
Module action -- no sound indication.
¾
Gas extinguishing device action -- “tick” sound.
¾
Delayed activation of devices by automatic C&E equation - slow “tick” sound
(0.5s on).
The FACP gives slow “tick” sound (1s on)when fault occurs.
The FACP will give sound of higher priority if two types of event occur simultaneously.