GST200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
The Intelligent Solution
Page 33
n fire alarm condition, the system needs to be silenced before RESET operation.
6.3.2 Enable
and
Disable
The disabling/enabling of devices is mainly used when a trouble condition of a device
cannot be removed in time. This device can then be temporarily disabled, and enabled
after it’s repaired.
The disabling/enabling of delay can be set as needed. For example, if there is person
on duty, the system delay can be enabled, so that the system can select delay by C&E
equation or by the pre-set local delay in case of an alarm. If there is nobody on duty, the
delay can be disabled and the system outputs immediately.
Pressing
ENABLE/DISABLE
, the screen will be shown as in Fig. 6-16.
*Disable / Enable*
1 Disable Devices
2 Enable Devices
3 Dis/En-able Delays
Fig. 6-16
6.3.2.1 Disabling
a
Device
In the screen shown in Fig. 6-16, input number “1”, you can enter disable screen as
shown in Fig. 6-17, where you are able to disable devices. The panel provides two
methods for disabling devices. You can disable a single device (single-device disable)
or all devices of a zone or multiple devices by using asterisk mark “*” (multi-device
disable). The wildcard character “*” represents any number between 0 and 9.
Disable
Z000 C000 T00 NoDefine
Fig. 6-17
You can input 3-digit number or asterisk after “Z” for zone number.
You can input 3-digit number or asterisk after “C” for device code.
You can input 2-digit number or asterisk after “T” for device type.
1
Example for disabling a single device
In order to disable the photoelectric smoke detector No. 001 in Zone No. 1, you need to
input zone number 001, device number 001 and device type 03 in sequence.
2
Examples for disabling multiple devices