![GST GST200 Скачать руководство пользователя страница 13](http://html1.mh-extra.com/html/gst/gst200/gst200_installation-and-operation-manual_2275587013.webp)
GST200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
The Intelligent Solution
Page 10
Key: Pressed for evacuation in fire alarm conditions.
3.1.4.4 SILENCE
Key
Fixed to key No. 32.
Indicator:
Illuminates the yellow LED after
SILENCE
key is pressed, and goes off
after system reset or
EVAC
key is pressed.
Key: For silencing the system after
EVAC
key is pressed for evacuation.
3.2 Configuration
3.2.1 Standard
Configuration
A standard FACP consists of main board, loop interface board, power supply, display
area, and zone indication and manual intervention panel (ZCP).
Main board
Main board is the core of the FACP, which contains CPU and interfaces to other
main parts and optional parts.
Loop interface board
It is the signal interface of the FACP, contain ports for communication, detection,
fire alarm output and fault output etc. The loop interface board connects field
devices and the FACP into a complete fire alarm system.
Power supply
It provides power to the main board, loop interface board and printer. Its backup
feature ensures that devices registered during commission will not be lost in case
of power fault.
Display and operation part
This part is used to indicate and display different status of the system, and enables
relative operations through keypad (browsing, setting, printing and etc).
Zone indication and manual intervention panel (ZCP)
The ZCP can indicate fire alarm, fault/disable state of corresponding devices, and
start and stop them accordingly.
1.1.2
Optional Units
P-9901 Printer
It is a built-in micro printer. With dot matrix printing it can print 96 kinds of ASCII
code characters (capital or lower case of Latin letters, figures and symbols), 128
coded non-standard characters and chart symbol (some Chinese characters,
Greek letters, block symbol etc.), and 16 code characters (6×7 dot) which can be
defined by the user through program, and replace any code font by commanding,
so as to print characters of different language.
Communication card
GST200 Intelligent Fire Alarm Control Panel (FACP) provides a multi-functional
Содержание GST200