GST200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
The Intelligent Solution
Page 43
sounders. Inputting number 2, the sounder will not be able to be silenced within 3
minutes after the first fire alarm.
6.4.5.3 Disabling
Password
Inputting number 3 will enter the screen for disabling password, as in Fig. 6-42.
Choosing “1” means to disable this function and access password will be required for
proper operation. Choosing “2” is to enable this function so that access password is not
required.
Fig. 6-42
*
Disable Password *
1.
Disable
2.
Enable
6.4.6
Initialization of System
Input “6” on the screen shown in Fig. 6-29, you can initialize system data.
6.4.7
Viewing Supervisory Data of Addressable Devices
Input “7” on the screen shown in Fig. 6-29 to enter the window shown in Fig. 6-43.
Entering the equipment number and the order number can view the supervisory value of
addressable devices.
Fig. 6-43
GST CO., LTD.
Equipment Num:001
Order Number:002
Pressing different number keys represent different commands:
“0” represents the command “Polling”. If the displayed value is between 450
~
650,
the device is in normal operation; if it’s between 900
~
1200, the device is in alarm
status, and if it’s between 0
~
120, the device is in fault.
“1” represents “registration” command, and around 720 for normal status.
“2” represents the command for monitoring the commission status of I-9105R
beam detector. If the displayed value is between 680
~
750, this means the
commission is completed.
“15” means “Start” command, which can start the output of corresponding modules,
or light the alarm LED of addressable devices.
Other numbers are reserved for future expansion.