![GST GST200 Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/gst/gst200/gst200_installation-and-operation-manual_2275587011.webp)
GST200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
The Intelligent Solution
Page 8
PLANT CONTROL:
Yellow. Action message indication. It illuminates when there
are feedback signals from fire-protective plant.
DELAY MODE:
Yellow, it illuminates when the output is set in delay mode.
EXTINGUISHING SYSTEM RELEASE:
Yellow. It illuminates when connected gas
extinguishing equipment has been activated.
EXTINGUISHING SYSTEM REQUEST:
Yellow. It illuminates when the system is
ready to start the gas extinguishing equipment but the FACP is in release-disabled
or delayed state.
EXTINGUISHING SYSTEM PERMIT:
Yellow. It illuminates when extinguishing
system is enabled.
3.1.3
Description of Keys
SYSTEM:
System set-up key (manager password required), used for setting
system time, modifying operator password and manager password, setting network
system, setting beginning zone number, customized setup, system initialization
and viewing supervisory data of intelligent devices.
PRINT:
Printing mode setting (operator password required).
SELF TEST:
Pressing this key in standby state can test the visual and audible
indication of the panel (operator password required).
MODE:
Setting the panel to automatically start the gas extinguishing equipment or
not (operator password required).
START/STOP:
Start/stop the loop devices (operator password required).
ENABLE/DISABLE:
Enabling/disabling addressable devices and delay mode.
TAB/SEC:
For
setting up burglar mode (operator password required) in system
setting (SEC), or used for moving the cursor when entering text (TAB).
RESET:
Resetting the FACP (operator password required).
BROWSE:
Browsing definition of loop devices, communication devices and ZCP
devices.
LOG:
Looking through history record.
SCREEN:
Setting up the screen contrast, message display mode and browsing
cause and effect (C&E) equations.
MUTE:
Muting the FACP.
VIEW FAULT:
Viewing fault message.
LOCK:
Locking the keypad when it is unlocked.
:
Scroll among more than one piece of displayed messages.
,
ESC:
Canceling or quitting the operating menu. If it’s pressed while the FACP is
displaying messages, it will resume to display messages of the highest level.
VIEW DISABLE:
Viewing disabled messages.
ENTER:
Confirming inputs to be valid. In normal standby state, pressing it can
Содержание GST200