GST200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
The Intelligent Solution
Page 34
In order to disable all devices with type number 001
~
11 of Zone No.1, you need to
input in sequence the zone number 001, device code *** and device type **.
For device with type number 12
~
65, the asterisk mark is not allowed for the type
number.
3
Example for disabling sounder circuit output (Sounder A) and F.P.E.
The address for the Sounder circuit output on the loop interface board is 240, and its
device type is 55-SounderA. The address for F.P.E. Output is 241, and its device type is
65-F.P.E. The system defaults these two outputs into zone No .0. To disable them, you
need to operate as follows:
You can disable sounder circuit output by inputting in sequence the zone number
000, device type 240 and device type 55. The panel will light the
SOUNDER
FLT/DISABLE
LED.
You can disable F.P.E output by inputting in sequence the zone number 000, device
type 241 and device type 65. The panel will light the
F.P.E FLT/DISABLE
LED.
6.3.2.2 Enabling
Devices
In the screen shown in Fig. 6-16, input number 2, you can enter device enable screen as
shown in Fig. 6-18. Same as disabling devices, you can also enable a single device or
multiple devices with the same methods of disabling them.
Enable
Z000 C000 T00 NoDefine
Fig. 6-18
6.3.2.3 Disabling/Enabling Delays
Inputting number 3 in the screen shown in Fig. 6-16 can enter the screen of
disabling/enabling delays, as shown in Fig. 6-19 Here you can select to enable or
disable the system delay.
Fig. 6-19
* Delay Mode*
1.
Disable
2.
Enable
In the above screen, you can operate as follows: