GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 5
1 Product Description
GST-M200 Intelligent Fire Alarm Control Panel (FACP) complies to UL 864 standard with
features of easy installation, operation, and maintenance. All circuit boards are installed in
a metal cabinet, providing a complete fire control system for most applications.
Inventory
GST-M200 is delivered with all components installed. When the shipment is received,
check to make certain that all accessories have been included:
Cabinet key
Manual
1.1 Features and Options
Single ring loop which meets Style 6 (Class A) requirements
or Style 7 (Class A)
requirements when utilizing Model C-M9503 Isolators
.
240 addressable devices.
Notification Appliance Circuit (NAC): Two Style Y (Class B) SOUNDER ports,
regulated, rated current 0.001A, maximum current 1.2A. The FACP is able to
synchronize all sounders (Max 12) by connecting a synchronization module with each
of the two NACs.
2.4A total power for NACs and 0.75A for regulated 24 VDC auxiliary power outputs.
5.3A total system power (includes battery charger).
Three fixed relay outputs: Alarm/Fault/Supervisory (for common use).
EIA-232 PC interface for GMC communication system - no connection (for future
use).
RS485 communication interface for networking - no connection (for future use).
LCD display unit of 128 x 64.
Real-time clock.
History file with 1,000 - event capacity.
Advanced fire technology features:
Maintenance alert by LED indication.
Point trouble identification.
“Walk test”, silent or audible.
PAS (Positive Alarm Sequence) per point (NFPA 72 compliant).
Auto silence timer option per NAC, the time duration is 5 minutes.
Password and key-protected nonvolatile memory.
User programmable password.
Fully programmable from local keypad.
Signaling Line Circuit (SLC) operates up to 4000ft through twisted pair with cross
Содержание GST-M200