2.5 Notification Appliance Circuits (NAC)
There are two Style Y (Class B) NAC outputs on the loop interface board. Each circuit is
capable of 1.2A of current. Total current in alarm for all external devices cannot exceed
2.4A. Use System Sensor
’s UL listed sounders (see Section 1.6.5) that can work at
regulated 24VDC. Circuits are regulated, supervised and power-limited.
2 Style Y (Class B) Notification Appliance Circuits,
regulated , supervised and power-limited - 4.7 kOhm EOL