GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 3
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING
- Several different sources of power can be connected to the fire alarm control
panel
.
Disconnect all sources of power before servicing. Control unit and associated
equipment may be damaged by removing and/or inserting cards, modules, or
interconnecting cables while the unit is energized. Do not attempt to install, service, or
operate this unit until this manual is read and understood.
CAUTION
-
System Reacceptance Test after Software Changes.
To ensure proper
system operation, this product must be tested in accordance with NFPA 72 Chapter 7
after any programming operation or change in site-specific software. Reacceptance
testing is required after any change, addition or deletion of system components, or after
any modification, repair or adjustment to system hardware or wiring. All components,
circuits, system operations, or software functions known to be affected by a change must
be 100% tested. In addition, to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected by the change, up to a
maximum of 50 devices, must also be tested and proper system operation verified.
This system
meets NFPA requirements for operation at 0-49°C/32-120° F and at 93% RH
(non condensing), and applies to be installed in the dry indoor environment.
Like all solid state electronic devices, this system may operate erratically or can be
damaged when subjected to lightning-induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will
reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an
increased susceptibility to nearby lightning strikes.
Consult with the Technical Services
Department if any problems are anticipated or encountered.
Disconnect AC power and batteries
prior to removing or inserting circuit boards. Failure to
do so can damage circuits.
Remove all electronic assemblies
prior to any drilling, filing, reaming, or punching of the
enclosure. When possible, make all cable entries from the sides or rear. Before making
modifications, verify that they will not interfere with battery, transformer, and printed circuit
board location.
Do not tighten screw terminals
more than 9 in-lbs. Over-tightening may damage threads,
resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This
system contains static-sensitive components. Always ground yourself with a proper wrist
strap before handling any circuits so that static charges are removed from the body. Use
static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions
in the installation, operating, and programming manuals. These
instructions must be followed to avoid damage to the control panel and associated
equipment. FACP (Fire Alarm Control Panel) operation and reliability depend upon proper
installation by authorized personnel.