GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 42
Fig. 4-8
4.11.4 Disable Point
Selecting
“5. Disable Point” in the screen of Fig. 4-5 can view information of disabled
devices.
5 Selecting and Locating Batteries
5.1 NFPA Battery Requirements
NFPA 72 Local and Proprietary Fire Alarm Systems require 24 hours of standby power
followed by 5 minutes in alarm.
5.2 Calculating the Battery Size
The size of batteries needed for a system can be calculated according to the following
tables.
Table 5-1
Device
Current
Standby Current
Number x lj = Total
Alarm Current
Number x la =Total
GST-M200
1 x 0.34A = 0.34A
1 x 0.45A = 0.45A
Smoke detector
I-9102(UL) / JTY-GD-G3
N x 0.0008A =
N x 0.002A =
Heat detector
I-9103(UL) / JTY-ZCD-G3N
N x 0.0008A =
N x 0.002A =
Loop isolator
C-9503 / GST-LD-8322
N x 0.005A =
N x 0.005A =
Input module
I-M9300 / GST-LD-8300
N x 0.001A =
N x 0.003A =
Output module
I-M9301 / GST-LD-8301
N x 0.001A =
N x 0.003A =
LC200 Loop card
1 x 0.135A =0.135A
1 x 0.135A = 0.135A
ENTER
Browse E&C
Sum:003
E&C 01
E&C 02
E&C 03
Browse E&C
12343350&112341111&1234567
8=32150111