GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 43
P-9930 Ancillary device
1 x 0.05A=0.05A
1 x 0.05A =0.05A
P-M9930 Modbus card
1 x0..05A =0.05A
1 x 0.1A = 0.05A
P-M9960A network card
1 x 0.05A= 0.05A
1 x 0.11A =0.05A
Loop isolator
C-M9503
N x0.0015A =
N x 0.002A =
Heat Photoelectric Smoke Detector
DI-M9101
N x 0.0008A =
N x 0.0018A =
(
without remote indicator
)
N x 0.0018A =
(
with remote indicator
)
Photoelectric Smoke Detector
DI-M9102
N x 0.0008A =
N x 0.0018A =
(
without remote indicator
)
N x 0.0018A =
(
with remote indicator
)
Intelligent Rate
of
Rise
and
Fixed Temperature Heat Detector
DI-M9103
N x 0.0006A =
N x0.0015A =
(
without remote indicator
)
N x0.0035A =
(
with remote indicator
)
Total
Total standby current
Total alarm current
Table 5-2
System Status
Battery requirement
(
Unit: Ah
)
Required standby time Tj (hour)
Total standby current
×
Tj
Required alarm time Ta (hour)
Total alarm current
×
Ta
Work time for maximum load Tw
(hour)
4.3A (maximum load current) x Tw
Total
The sum of the above three items is the maximum
battery capacity required by the FACP.
Please select batteries that meet or exceed the total ampere hours calculated in Table 5-1
and 5-2. The control panel can charge batteries less than 20Ah. Batteries larger than
20Ah require a UL listed external battery charger.
Note: When batteries over 20Ah are used, they should be put into a separate battery
box, which is not provided. The battery box must be located in the same room
with the fire alarm control panel.
6 Default Programming
Program Option
Factory Default
BANNER
GST CO., LTD.
Maintenance Password
Empty
Master Password
11111111
PAS Timer
0
Userwords
Undefined
Userdefine
Userdefine01-15
E&C
Undefined
Device address
(
1-242
)
Zone: 001
Type: 0 Undefined
Walktest: on
PAS: off
Silenceable: on
Autosilence: off
Walk Test
Off