GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 38
Fig. 4-3
Description:
The first line: ALARM means alarm message.
The second line:
“001” is the number of the message and “040” is the number of total
messages.
“
√
” is the acknowledgement mark.
The third line:
“SMOKE (PHOTO)” is device type and “C001” is device address.
The fourth line:
“16:34 0112” is the time the event occurs in the sequence of Hour,
Minute, Day, Mouth;
“Z001” is the zone number.
The fifth and sixth line: Device description, maximum 32 characters.
4.6 Waterflow Circuits Operation (For Future Use)
Only the device whose type is 11 can carry out Waterflow Circuits operation. Its operating
method is the same as
4.5 Alarm Operation
.
4.7 Supervisory Operation
The devices whose types are between 11 and 19 can carry out supervisory operation,
which is similar to alarm operation excluding the following difference.
Sound of the panel pulses ½ second On and ½ second Off.
The
SUPERVISORY
LED turns on.
The LCD displays the status label
Active Supervisory
along with the device name,
type, address, associated zones and time/date.
The device defined as supervisory relay is activated.
Silenced alarms resound.
Autosilence timer is not started.
Write history buffer.
A typical Supervisory event would be displayed as follows:
ALARM
001 0f 040
√
SMOKE (PHOTO) C001
16:34 0112 Z001
description
:
(32 char, 2 line
)
(40 char, 2 line)