GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 24
Fig. 3-11
Here the user can define some commonly used phrases, which can then be used later
when defining devices or entering other text to save programming time. To do this, the
user needs to input the number of the text first, then the text itself (12 characters at most),
like
“Detector” in the above example. Please refer to Section 3.1 for how to edit the text.
Please note that there is no text available yet when defining the first text.
3.4.2 Point Debug
Selecting
“1. Point Debug” in the screen in Fig. 3-2, the screen for viewing supervisory
value of addressable devices will be displayed, as in Fig. 3-12:
Fig. 3-12
Entering the equipment number and the order number can view the supervisory value of
addressable devices.
Pressing different number keys represent different commands:
Key
“0” represents the command “Polling”. If the displayed value is between 450~650,
the device is in normal operation; if it
’s between 900~1200, the device is in alarm
status, and if it
’s between 0~120, the device is in fault.
“1” represents “registration” command, and 720 for normal.
“2” represents the command “viewing dynamic data” for reading real time data of
detectors.
“15” means “Start” command, which can start the output of corresponding modules, or
light the alarm LED of addressable devices.
Other numbers are reserved for future expansion.
* My Words Setting *
Please Input
Words Number: 01
t[Detector ]
16/09-09 V***
Equipment Num: 001
Order Number: 002