GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 33
LCD contrast can be changed by pressing the up and down key.
3.8.3
NAC Setup
Selecting
“3. NAC Setup” in the screen of Fig. 3-25 can set NAC1 and NAC2, as in the
following figure:
Fig. 3-25
NAC1 and NAC2 can be respectively set up with the same method. Here we take NAC1
as an example. Choosing
“1. NAC1” will enter the following screen:
Fig. 3-26
The Coding feature allows the programmer to select the type of output that the loop
interface board notification appliances will generate when activated. Four optional modes
are available by selecting among number 0, 1, 2 and 3:
0: Disable - NAC1 is disabled.
1: Steady - a continuous output with no coding.
2: March Time - 120 ppm (pulse-per-minute) output.
3: Temporal - ½ second on, ½ second off, ½ second on, ½ second off, ½ second
on, 1½ second off.
“Silenceable” provides options between silencing NAC1 or not. Choosing number “0”,
NAC1 will not be silenced; choosing number
“1”, it will be silenced.
“Auto Silence” provides options to automatically silence NAC1 or not. Number “0” means
automatic silencing is not allowed, and
“1” allows it to be automatically silenced.
*NAC Setup*
1.
NAC1
2.
NAC2
NAC1 Setting
Coding:
1 Steady
Silenceable: 0 OFF
AutoSilence: 0 OFF