GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 14
380
113.5
640
Fig. 2-2
2.2 Power
WARNING: Several different sources of power can be connected to this
panel. Disconnect all sources of power before servicing. The panel and
associated equipment may be damaged by removing and/or inserting cards,
modules or interconnecting cables while this unit is energized.
2.2.1 AC Power and Earth Ground Connection
Primary power required for the FACP is 120VAC, 60 Hz, 2.4A or 220VAC, 50 Hz, 1.2A for
the FACP. Over-current protection for this circuit must comply with Article 760 of the
National Electrical Code (NEC) and/or local codes. Use 14AWG (2.00mm
2
) or larger wire
with 600 volt insulation rating. Make certain that the AC mains circuit breaker is off before
wiring any connections between the mains and the control panel. Connect power supply
to the Terminal XT1, as shown in Fig. 2-3.
Note: Verify all cables are correctly
connected before connecting power supply.