GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 37
will turn on the
AC FAULT
LED, a ground fault will turn on the
GROUND FAULT
LED, etc.
For addressable devices connected to the SLC loop, the following is a typical message
that could appear on the LCD display for a device trouble:
Fig. 4-2
Description:
The first line:
“TROUBLE” means there is trouble message.
The second line:
“001” is the number of this message, and “040” is the number of total
messages.
“
√
” is the acknowledgement mark.
The third line:
“SMOKE (PHOTO)” is device type and “C001” is device address.
The fourth line
: “16:34 0112” is the time the event occurs in the sequence of Hour,
Minute, Day, Mouth;
“Z001” is the zone number.
The fifth and sixth lines: Device description
,
maximum 32 characters.
4.5 Alarm Operation
Alarm operation is similar to trouble operation with the following differences:
Devices with type number less than 12 can give alarm signal.
Sound of the panel produces a steady output as opposed to a pulsed output.
The
FIRE ALARM
LED turns on.
The LCD displays
Alarm
along with the device name, type, address, associated
zones and time/date.
Alarms are self-latched and will not be cleared automatically.
Starts the device according to the E&C equation.
Autosilence timers are started.
Devices defined as alarm relay are activated.
Write history buffer.
A typical alarm display would be as illustrated below:
TROUBLE
001 0f 040
√
SMOKE (PHOTO) C001
16:34 0112 Z001
description
:
(32 char, 2 line)