GST-M200 Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 20
messages, control panel functions, etc.
Maintenance password is used by a qualified operator to access features such as
Autoprogram, Disable/Enable, Walk test and Configure Item.
3.4 Programming (Master)
Select
“2. Programming” in the screen shown in Fig. 3-1, the system will request for
password. If master password is entered, the LCD will display the messages shown in
Fig. 3-2.
Fig. 3-2
Selecting
“1. Point Debug” by entering “1” to view supervisory value of
addressable devices.
Selecting
“2. Point Edit” by entering “2” to define SLC addressable devices.
Selecting
“3. Network Setup” by entering “3” to set the FACP into network.
Selecting
“4. Event & Command” by entering “4” to edit E&C equation.
Selecting
“5. System Setup” by entering “5” for system setting.
3.4.1 System Setup
Select
“5. System Setup” in the screen of Fig. 3-2 to enter the screen shown in Fig. 3-3.
Fig. 3-3
Selecting
“1. Clear Program” by entering “1” to clear the memory and restore
factory default.
Selecting
“2. Banner” by entering “2” to edit the banner contents.
*Programming*
1
.
Point Debug
2
.
Point Edit
3
.
Network Setup
4
.
Event & Command
5
.
System Setup
* System Setup *
1.
Clear Program
2.
Banner
3.
Password Change
4.
Timers
5.
Defined SLC Type
6.
My Words